or
AC 1000A True RMS Clamp on
AC 1000A True RMS Clamp on or
Digital Clamp Power Meter ( DPM-041)
AC 1000A True RMS Clamp on
Power Meter
Model : DPM-041
Features:
Power measure of Active power (KW), Reactive power
(KVAR), Apparent power (KVA), Power Factor (PF)
PF (cos O) for 3O4W, 3O3W, 1O2W, 1O3W
Triple display: KW+V+A easy to read
AC current up to 1000A, AC voltage up to 600V
INRUSH (100mS), HOLD and PEAK functions
MAX and MIN recorded functions
Auto power off (10 mins), Black-light
Dimensions of conductor: O35mm
EN61010-1 Approval. Over-Voltage Category III 1000
Specifications:
AC 1000A True RMS Clamp on Model: DPM-041
SPECIFICATIONS CE Mark Safety Approval
AC Current (True RMS)
Range: 0.0 to 600.0A, 600A to 1000A
Resolution: 0.1A/1A
Accuracy: ±(1.5%rdg+10dgts) on 50Hz to 60Hz
±(3.5%rdg+10dgts) on 45Hz to 400Hz
AC Voltage (True RMS)
Range: 0.0 to 600.0V
Resolution: 0.1V
Accuracy: ±(1%rdg+5dgts) on 20Hz to 100Hz
±(6%rdg+5dgts) on 100Hz to 400Hz
Input impedance: 1MΩ
Power Measurement Accuracy
To make sure measuring accuracy, clamp the jaw several
times to align the contact surface in place to get the optimal
measuring results before you take measurement.
Single phase or three phase load with sine wave input at